Control Valve Blocked In Gas Service
Hi. I'm new here, so my first question concerns a problem we've had with a control valve. First, a few details:
Valve
 is used in a spillback system on a Refinery Crude Unit. The valve is on
 a line from the discharge vessel (we'll call it vessel 3, operating 
pressure  6-7kg/cm) of a compressor back to the suction vessel (Vessel 
2, operating pressure approx 1kg/cm). The valve is controlled from a 
pressure transmitter (via Honeywell TDC & 4-20mA o/p, then i/p) on 
another vessel ('vessel 1') which is linked to vessel 2 with a common 
line.
When the pressure drops too low on vessel 1 (and equally 
low on the vessel 2) the valve should open to recirculate the gas and 
thus increase the pressure in vessels 1&2.
The product is 
C3/C4s. Uncertain of the temperature its at, but it makes the pipework 
warm to touch, so obviously fairly hot (will post temp when I've 
checked).
The valve is a 3" Blakeborough BV(500 or 900) globe 
valve, =% plug, air fail closed, air on top of actuator to open (spring 
forces valve up to close).
The issue with the valve is that 
operations have been claiming that the valve will not control and 
believe there is no flow through the line. The valve is awkward to check
 as it is in split-range control with a second valve which opens to 
flare if vessel 1 pressure rises too high, so operations are 
uncomfortable to allow tests without full written procedures etc. 
However I am certain that the valve stem is moving, so I thought it was 
possible the stem was snapped inside or valve plug jammed.
Thermography
 was carried out on the valve and put the temperature of the body 
upstream at 27 deg C and downstream at 11 deg C, although I suspect the 
upstream body temp is higher than that.
Process engineers then 
had both gate block valves and the control valve body x-rayed. This 
shows that the block valves are both clear. It also more importantly 
shows that the valve plug is not seated in the valve, so I believe that 
it is physically open.
When the bypass valve was opened I have 
been told (although as I did not witness this I do not know how far open
 the valve was) the downstream temperature increase.
Has anyone 
got any suggestions as to what could be the issue? I suspect that the 
difference in temperature is due to the Joule-Thomson effect, and that 
opening the bypass valve (which I believe is a gate valve?) the D.P. was
 reduced so the temperature changed stopped.
However I cannot 
figure out why the valve is not having any control. Is it possible the 
gas is cooling to the point of icing up around the plug, reducing 
flow?!? Or could the wrong plug type be causing this? Any suggestions?
Removing
 the valve for inspection sounds obvious, but it is positioned awkwardly
 with little access to use a crane. I'm thinking about trying to block 
it in and drop the bottom flange off the valve to check inside, but 
again this will require a mountain of paperwork to do.
no control means that the valve is not accomplishing what it takes to operate the plant.
could be sizing, i.e. flow requirements greater than the valve was sized for, etc.
split
 ranging the flare valve with the spillback valve is a bit worrying. 
While it should not be a problem, I'd feel better if it had its own 
controller and setpoint.
By no control I mean the valve position seems to have no effect on the 
pressure in the vessel. The pressure in Vessel 1 is currently just 
relying on the pressure upstream to stay high enough at present. The 
process engineers continue to insist that the valve cannot be opening 
because there appears to be 'no control'. I've checked the line 
personally in the field and there are no block valves closed to prevent 
it functioning.
I'm wondering whether to fit pressure gauges to 
each of the vent/drain valves each side of the valve to check, and if 
the D.P. across the valve changes depending on valve position then I 
will be able to rule out the valve being closed.
Vessel 1, 2 and 3
 all have PSVs and I believe Vessel 1 also has a high Pressure shutdown 
on it, but I agree different loops would have been better. Unfortunately
 I was not at the Refinery when it was installed. The other drawback is 
that at present, both I/Ps have been wired in series, so I cannot even 
break the current loop or the flare valve will be unusable. Its poor 
design, but I don't think its whats causing the valve not to control.
I
 would have thought that the valve would still have some effect if it 
was undersized, unless the original design group got it drastically 
wrong (not impossible...)
I don't think you have a broken stem because I believe  you would get full flow most of the time. 
I scrolled thru the Blakeborough catalog.
Not
 every manufacturer shows everything in the catalog, but the way I read 
it the 500 and 900 only work in the pull-up-to-open mode.  The 800 is 
the top-and-bottom-guided, invertible body that <might> be push 
down to open.  So if you are sending the valve an increasing air signal 
to open, you may be closing it.  Obviously then your control would be 
"challenged". Just when you are calling for a lot of flow, you get 
bupkus.   The "quick" fix would be reversing the positioner action, but 
the proper repair would be replacing the actuator with a 
spring-to-push-down design.  
If it is an 800, there are top and 
bottom flanges on the body.  Push-down-to-open would likely then be 
accompanied with at least inverted lettering on the casting. You can 
change an invertible-body valve from direct to reverse by flipping the 
body and screwing the valve stem into the other end of the valve 
plug.  You'll need gaskets, and whatever locking device they use on the 
stem-to-plug connection. ( I have seen pins used)
It's something to check for.....
Sorry, I've just looked at the valve catalogue and I'm pretty sure it is
 a Blakeborough BV803. It is top and bottom guided (one suggestion was 
that there may be debris in the bottom guide preventing it from moving 
down) and it has a 'v'-port plug.
You're right in saying that if the stem was to have snapped the valve would have fallen wide open and allowed full flow.
The
 positioner (Fisher 3560 I think, so a force balance positioner using a 
flapper/nozzle and bellows arrangement) is set to reverse action, so 
with the output from the local current-to-pressure transducer giving an 
output of 3-9psi (split-range), the positioner has been set to give 
fully open at 3 psi input (high output from positioner), and fully 
closed at 9 psi input (low output from positioner).
The spring 
range on the valve is stated to be 6-18psi, and when I checked the valve
 on Thursday (I haven't been in work today, this is being written from 
home) the input to the positioner was 6 psi, and the positioner output 
was 11 to 12 psi. The valve stem appeared to be about 50% travel 
according to the plate (not a reliable guide, but its an indication of 
sorts).
So I think the valve is working, but something is not 
quite right in the system, or the valve is wrongly specced for the 
service...
MORE NEWS



