Control Valve Blocked In Gas Service
Hi. I'm new here, so my first question concerns a problem we've had with a control valve. First, a few details:
Valve
is used in a spillback system on a Refinery Crude Unit. The valve is on
a line from the discharge vessel (we'll call it vessel 3, operating
pressure 6-7kg/cm) of a compressor back to the suction vessel (Vessel
2, operating pressure approx 1kg/cm). The valve is controlled from a
pressure transmitter (via Honeywell TDC & 4-20mA o/p, then i/p) on
another vessel ('vessel 1') which is linked to vessel 2 with a common
line.
When the pressure drops too low on vessel 1 (and equally
low on the vessel 2) the valve should open to recirculate the gas and
thus increase the pressure in vessels 1&2.
The product is
C3/C4s. Uncertain of the temperature its at, but it makes the pipework
warm to touch, so obviously fairly hot (will post temp when I've
checked).
The valve is a 3" Blakeborough BV(500 or 900) globe
valve, =% plug, air fail closed, air on top of actuator to open (spring
forces valve up to close).
The issue with the valve is that
operations have been claiming that the valve will not control and
believe there is no flow through the line. The valve is awkward to check
as it is in split-range control with a second valve which opens to
flare if vessel 1 pressure rises too high, so operations are
uncomfortable to allow tests without full written procedures etc.
However I am certain that the valve stem is moving, so I thought it was
possible the stem was snapped inside or valve plug jammed.
Thermography
was carried out on the valve and put the temperature of the body
upstream at 27 deg C and downstream at 11 deg C, although I suspect the
upstream body temp is higher than that.
Process engineers then
had both gate block valves and the control valve body x-rayed. This
shows that the block valves are both clear. It also more importantly
shows that the valve plug is not seated in the valve, so I believe that
it is physically open.
When the bypass valve was opened I have
been told (although as I did not witness this I do not know how far open
the valve was) the downstream temperature increase.
Has anyone
got any suggestions as to what could be the issue? I suspect that the
difference in temperature is due to the Joule-Thomson effect, and that
opening the bypass valve (which I believe is a gate valve?) the D.P. was
reduced so the temperature changed stopped.
However I cannot
figure out why the valve is not having any control. Is it possible the
gas is cooling to the point of icing up around the plug, reducing
flow?!? Or could the wrong plug type be causing this? Any suggestions?
Removing
the valve for inspection sounds obvious, but it is positioned awkwardly
with little access to use a crane. I'm thinking about trying to block
it in and drop the bottom flange off the valve to check inside, but
again this will require a mountain of paperwork to do.
no control means that the valve is not accomplishing what it takes to operate the plant.
could be sizing, i.e. flow requirements greater than the valve was sized for, etc.
split
ranging the flare valve with the spillback valve is a bit worrying.
While it should not be a problem, I'd feel better if it had its own
controller and setpoint.
By no control I mean the valve position seems to have no effect on the
pressure in the vessel. The pressure in Vessel 1 is currently just
relying on the pressure upstream to stay high enough at present. The
process engineers continue to insist that the valve cannot be opening
because there appears to be 'no control'. I've checked the line
personally in the field and there are no block valves closed to prevent
it functioning.
I'm wondering whether to fit pressure gauges to
each of the vent/drain valves each side of the valve to check, and if
the D.P. across the valve changes depending on valve position then I
will be able to rule out the valve being closed.
Vessel 1, 2 and 3
all have PSVs and I believe Vessel 1 also has a high Pressure shutdown
on it, but I agree different loops would have been better. Unfortunately
I was not at the Refinery when it was installed. The other drawback is
that at present, both I/Ps have been wired in series, so I cannot even
break the current loop or the flare valve will be unusable. Its poor
design, but I don't think its whats causing the valve not to control.
I
would have thought that the valve would still have some effect if it
was undersized, unless the original design group got it drastically
wrong (not impossible...)
I don't think you have a broken stem because I believe you would get full flow most of the time.
I scrolled thru the Blakeborough catalog.
Not
every manufacturer shows everything in the catalog, but the way I read
it the 500 and 900 only work in the pull-up-to-open mode. The 800 is
the top-and-bottom-guided, invertible body that <might> be push
down to open. So if you are sending the valve an increasing air signal
to open, you may be closing it. Obviously then your control would be
"challenged". Just when you are calling for a lot of flow, you get
bupkus. The "quick" fix would be reversing the positioner action, but
the proper repair would be replacing the actuator with a
spring-to-push-down design.
If it is an 800, there are top and
bottom flanges on the body. Push-down-to-open would likely then be
accompanied with at least inverted lettering on the casting. You can
change an invertible-body valve from direct to reverse by flipping the
body and screwing the valve stem into the other end of the valve
plug. You'll need gaskets, and whatever locking device they use on the
stem-to-plug connection. ( I have seen pins used)
It's something to check for.....
Sorry, I've just looked at the valve catalogue and I'm pretty sure it is
a Blakeborough BV803. It is top and bottom guided (one suggestion was
that there may be debris in the bottom guide preventing it from moving
down) and it has a 'v'-port plug.
You're right in saying that if the stem was to have snapped the valve would have fallen wide open and allowed full flow.
The
positioner (Fisher 3560 I think, so a force balance positioner using a
flapper/nozzle and bellows arrangement) is set to reverse action, so
with the output from the local current-to-pressure transducer giving an
output of 3-9psi (split-range), the positioner has been set to give
fully open at 3 psi input (high output from positioner), and fully
closed at 9 psi input (low output from positioner).
The spring
range on the valve is stated to be 6-18psi, and when I checked the valve
on Thursday (I haven't been in work today, this is being written from
home) the input to the positioner was 6 psi, and the positioner output
was 11 to 12 psi. The valve stem appeared to be about 50% travel
according to the plate (not a reliable guide, but its an indication of
sorts).
So I think the valve is working, but something is not
quite right in the system, or the valve is wrongly specced for the
service...
MORE NEWS